A Change of Air
Energy
saving, ventilation and health.
In
the UK an appreciable proportion of total energy consumption can be
ascribed to heating buildings, and of this energy a significant
amount is used to heat air. If the number of air changes per hour
(ACH) is unnecessarily high, energy is wasted. This post concentrates
on domestic buildings, in which a reduction in ACH can often be
achieved by cheap and simple means, giving a rapid return on
expenditure through lowered energy costs. However, the ACH figure for
a house should not be reduced below the minimum needed for the health
of its occupants and the preservation of its fabric. In order to know
whether the ACH for a dwelling should be reduced, the actual ACH
value is needed, and to know by how much it can safely be cut, the
minimum figure is required.
Pressurisation
is one method of measuring the actual ACH figure, and is described in
ATTMA Technical Standard L1 Measuring Air Permeability in the
Envelopes of Buildings, 2016 (open access). Pressure within the
building is raised by a known amount above atmospheric pressure, and
the rate of air flow into the building through the pressurising
device is measured, and equated to the total air leakage. The
pressure difference used is typically 50 Pa, and the measured
permeability, expressed as rate of volume change per unit of surface
area, is adjusted by a standard factor to give the leakage value for
the unpressurised building. The result is clearly dependant on this
factor, and its validity is disputed: see The Origin and
Application of Leakage-Infiltration Ratios by
Jones, Persily, and Sherman (available at Researchgate).
A
second approach to estimating ACH depends on an energy balance
calculation. Here the energy input to the building must be known, as
well as the total energy lost through the fabric. Given these two
figures, the difference is taken to represent the energy lost to air
changes. From the volume of the building, and the appropriate air
parameters and temperatures, the rate of change of air in the
building can be calculated. However, in many cases it may only be
possible to reach an approximation to the total energy loss, due to
lack of thermal data on the building structure, and in these cases
the ACH figure derived must also be approximate. See: Estimating
the air change rates in dwellings using a heat balance approach by
Cosar-Jorda and Buswell, 2015 (open access).
By
either method, the ACH figure reached may be regarded in many cases
as having a wide margin of error, so that even if a minimum desirable
value for ACH is known, a cautious approach to reducing the air
change rate will seem advisable, to avoid inadvertently falling below
the minimum level.
One
source of information on minimum ACH figures is a standard of the
American Society of Heating, Refrigerating and Air Conditioning
Engineers, ASHRAE Standard 62.2. Ventilation and Acceptable Indoor
Air Quality in Low Rise Residential Buildings. This publication
may not be freely available, but a 2004 paper by M. H. Sherman
entitled ASHRAE’s First Residential Ventilation Standard
has open access. It provides data on recommended minimum ventilation
levels based on individual rooms within a house, and the number of
occupants.
More
direct methods of assessing air quality such as measurement of CO2
levels, may be needed to check that reductions in the ACH level
of a building remain within safe limits. This issue is discussed in
Smart homes and the control of indoor air quality by Alexandra
Schiewecka et al., 2018, (open access). Though the data in this paper
are based on Central Europe, the methods described are widely
applicable. Indoor CO2 levels above 2000ppm are regarded
as “unacceptable”, whereas levels below 1000ppm are taken as
“harmless”. Data are provided on the ventilation level needed in
a room of given volume with a specified number of occupants in order
to meet these two CO2 levels, and these suggest that one
or both levels may be exceeded at ACH rates considerable above those
met in passive house environments.
Comments
Post a Comment